heat recovery
recovery of heat rejected by the unit(s) whose primary control is in the cooling mode by means of either an
additional heat exchanger (e.g. a liquid chiller with an additional condenser) or by transferring the heat through
the refrigerating system for use to unit(s) whose primary control remains in the heating mode (e.g. variable
refrigerant flow)
2.12
indoor heat exchanger
heat exchanger which is designed to transfer heat to the indoor part of the building or to the indoor hot water
supplies or to remove heat from these
NOTE In the case of an air conditioner or heat pump operating in the cooling mode, this is the evaporator. In the case
of an air conditioner or heat pump operating in the heating mode, this is the condenser.
EN 14511-1:2004 (E)
6
2.13
outdoor heat exchanger
heat exchanger which is designed to remove heat from the outdoor ambient environment, or any other
available heat source, or to transfer heat to it
NOTE In the case of an air conditioner or heat pump operating in the cooling mode, this is the condenser. In the case
of an air conditioner heat pump operating in the heating mode, this is the evaporator.
2.14
heat recovery heat exchanger
heat exchanger assembly which is designed to transfer heat to the heat recovery medium
2.15
heat transfer medium
any medium (water, air, ...) used for the transfer of the heat without change of state. It can be:
¾ cooled liquid circulating in the evaporator;
¾ cooling medium circulating in the condenser;
¾ heat recovery medium circulating in the heat recovery heat exchanger
2.16
outdoor air
air introduced to the conditioned space through the unit from the outside
2.17
recycled air
air from the conditioned space through the unit and back to the conditioned space
2.18
exhaust air
air from the conditioned space through the unit to the outdoor side
2.19
water loop
closed circuit of water maintained within a temperature range on which the units in cooling mode reject heat
and the units in heating mode take heat
2.20
total cooling capacity
PC
heat given off from the heat transfer medium to the unit per unit of time, expressed in Watt
2.21
latent cooling capacity
PL
capacity of the unit for removing latent heat from the evaporator intake air, expressed in Watt
2.22
sensible cooling capacity
PS
capacity of the unit for removing sensible heat from the evaporator intake air, expressed in Watt
EN 14511-1:2004 (E)
7
2.23
heating capacity
PH
heat given off by the unit to the heat transfer medium per unit of time, expressed in Watt
NOTE If heat is removed from the indoor heat exchanger for defrosting, it is taken into account.
2.24
heat rejection capacity
heat removed by the heat transfer medium of the condenser per unit of time, expressed in Watt
NOTE This applies only to heat recovery liquid chilling packages.
2.25
heat recovery capacity
heat removed by the heat transfer medium of the heat recovery heat exchanger, per unit of time, expressed in (责任编辑:admin)