Tested EER ³ 0,85 X declared EER
Tested COP ³ 0,85 X declared COP
A.4.3 Second testing
If the result of test on capacity and/or EER/COP carried out on the first appliance is not in compliance with the
requirements given in A.4.2, a second test shall be carried out on one other appliance. This second test shall
meet the following criteria for cooling and heating mode as applicable:
Tested cooling and heating capacity ³ 0,88 X declared capacity
Tested EER ³ 0,85 X declared EER
Tested COP ³ 0,85 X declared COP
EN 14511-2:2004 (E)
14
Annex ZA
(informative)
Relationship of this document with EC Directives
This European Standard has been prepared under a mandate given to CEN by the European Commission
and the European Free Trade Association and supports essential requirements of EC Directive:
Energy Labelling Directive 02/31/EC
WARNING : Other requirements and other EU Directives may be applicable to the product(s) falling
within the scope of this standard.
Compliance with the clauses of this standard provides one means of conforming with the specific essential
requirements of the Directive concerned and associated EFTA regulations.
EN 14511-2:2004 (E)
15
Bibliography
[1] CEN/TS 14825, Air conditioners, liquid chilling packages and heat pumps with electrically drive
compressors for space heating and cooling – Testing and rating at part load conditions.