4.4.2 Output measurement for water-to-water and water-to-air units 4.4.2.1 Steady state conditions This condition is considered obtained and maintained when all the measured quantities remain constant without having to alter the set values, for a minimum duration of 1 h, with respect to the tolerances given in Table 4. Periodic fluctuations of measured quantities caused by the operation of regulation and control devices are permissible, on condition the mean value of such fluctuations does not exceed the permissible deviations listed in Table 4. 4.4.2.2 Measurement of heating capacity, cooling capacity and heat recovery capacity For the output measurement it is necessary to record all the meaningful data continuously. In the case of recording instruments which operate on a cyclic basis, the sequence shall be adjusted such that a complete recording is effected at least once every 30 s. The output shall be measured in the steady state condition. The duration of measurement shall be not less than 洁净网 35 min. 4.4.3 Output measurement for cooling capacity of air-to-water and air-to-air units 4.4.3.1 Steady state conditions This condition is considered obtained and maintained when all the measured quantities remain constant without having to alter the set values, for a minimum duration of 1 h, with respect to the tolerances given in Table 4. Periodic fluctuations of measured quantities caused by the operation of regulation and control devices are permissible, on condition the mean value of such fluctuations does not exceed the permissible deviations listed in Table 4. EN 14511-3:2004 (E) 15 4.4.3.2 Measurement of cooling capacity For the output measurement it is necessary to record all the meaningful data continuously. In the case of recording instruments which operate on a cyclic basis, the sequence shall be adjusted such that a complete recording is effected at least once every 30 s. The output shall be measured in the steady state condition. The duration of measurement shall be not less than 洁净网 35 min. 4.4.4 Output measurement for heating capacity of air-to-water and air-to-air units 4.4.4.1 General The test procedure consists of three periods: a preconditioning period, an equilibrium period, and a data collection period. The duration of the data collection differs depending upon whether the heat pump’s operation is steady state or transient. Annex C gives a flow chart of the procedure and pictorially represents most of the different test sequences that are possible when conducting a heating capacity test. 4.4.4.2 Preconditioning period The test room reconditioning apparatus and the heat pump under test shall be operated until the test tolerances specified in Table 4 are attained for at least 10 min. A defrost cycle may end a preconditioning period. If a defrost cycle does end a preconditioning period, the heat pump shall operate in the heating mode for at least 10 min after defrost termination prior to beginning the (责任编辑:admin) |