application rating conditions are published by the manufacturer or supplier
EN 14511-1:2004 (E)
9
2.43
basic multi-split system
split system incorporating a single refrigerant circuit, with one or more compressors, multiple indoor units
designed for individual operation and one outdoor unit. The system has no more than two steps of control by
either two compressors or by compressor unloading and is capable of operating either as an air-conditioner or
a heat pump. A system having a variable speed compressor where a fixed combination of indoor units is
specified by the manufacturer is also considered as a basic multi-split system
2.44
multiple circuit multi-split system
split system incorporating multiple refrigerant circuits, two or more single speed compressors, multiple indoor units
and an integrated heat exchanger in a single outdoor unit and is capable of operating either as an air conditioner
or a heat pump
2.45
modular multi-split system
split system air conditioner or heat pump incorporating a single refrigerant circuit, at least one variable speed
compressor or an alternative compressor combination for varying the capacity of the system by three or more
steps, multiple indoor units, each of which can be individually controlled, one or more outdoor units and is
capable of operating either as an air conditioner or a heat pump
2.46
modular heat recovery multi-split system
split system air conditioner or heat pump incorporating a single refrigerant circuit, at least one variable-speed
compressor or an alternate compressor combination for varying the capacity of the system by three or more
steps, multiple indoor units, each capable of being individually controlled and one or more outdoor units. This
system is capable of operating as a heat pump where recovered heat from the indoor units operating in the
cooling mode can be transferred to one or more units operating in the heating mode
NOTE This may be achieved by a gas/liquid separator or a third line in the refrigeration circuit.
2.47
rated capacity
capacity measured in the standard rating conditions
2.48
system capacity
capacity of the system when all outdoor and indoor units are operating in the same mode
2.49
system reduced capacity
capacity of the system when some of the indoor units are disconnected
2.50
system capacity ratio
ratio of the total stated cooling (heating) capacity of all operating indoor units to the stated cooling (heating)
capacity of the outdoor unit at the rating conditions
2.51
heat recovery efficiency
HRE
ratio of the total capacity of the system (heating plus cooling capacity) to the effective power input when
operating in the heat recovery mode
2.52
standard air
dry air at 20 °C and at standard barometric pressure of 101,325 kPa, having a mass density of 1,204 kg/m³
EN 14511-1:2004 (E)
10
3 Classification
The units are denominated in such a way that the heat transfer medium for the outdoor heat exchanger is (责任编辑:admin)