AD
Tested EER ³ 0,85 X declared EER Tested COP ³ 0,85 X declared COP A.4.3 Second testing If the result of test on capacity and/or EER/COP carried out on the first appliance is not in compliance with the requirements given in A.4.2, a second test shall be carried out on one other appliance. This second test shall meet the following criteria for cooling and heating mode as applicable: Tested cooling and heating capacity ³ 0,88 X declared capacity Tested EER ³ 0,85 X declared EER Tested COP ³ 0,85 X declared COP EN 14511-2:2004 (E) 14 Annex ZA (informative) Relationship of this document with EC Directives This European Standard has been prepared under a mandate given to CEN by the European Commission and the European Free Trade Association and supports essential requirements of EC Directive: Energy Labelling Directive 02/31/EC WARNING : Other requirements and other EU Directives may be applicable to the product(s) falling 洁净网 within the scope of this standard. Compliance with the clauses of this standard provides one means of conforming with the specific essential requirements of the Directive concerned and associated EFTA regulations. EN 14511-2:2004 (E) 15 Bibliography [1] CEN/TS 14825, Air conditioners, liquid chilling packages and heat pumps with electrically drive compressors for space heating and cooling – Testing and rating at part load conditions. (责任编辑:admin) |